The transformer oil gas chromatograph is suitable for the determination of the content of dissolved gas components in the insulating oil of the power system. A single injection can complete the full analysis of the content of 7 dissolved gas components in the insulating oil, and its minimum detection concentration of acetylene reaches 0.1ppm. The instrument is equipped with a large-screen LCD liquid crystal display interface, menu-driven Chinese operation, intuitive display, and convenient operation.
The instrument adopts a dual-column parallel split system, equipped with a thermal conductivity detector, a dual hydrogen flame detector, and a methane converter. It can complete the full analysis of H2, O2, CO2, CH4, C2H2, C2H4, and C2H6 in a single injection.
◆ Adopts a 320 x 240 dot matrix 5.7-inch ultra-large screen LCD Chinese display, displaying various temperatures and operating conditions in real time, with clear and intuitive content;
◆ Power-on self-test, wide-range self-diagnosis function, can accurately judge the fault location and alarm;
◆ Six independent temperature control channels (vaporization chamber and capillary vaporization chamber can be independently controlled), eight-stage temperature programming function;
◆ Overtemperature protection function: If any channel exceeds the set temperature, the instrument will automatically power off and alarm;
◆ Unique vertical heating device, making sample vaporization more reliable, minimizing the heat radiation generated by the vaporization chamber, and ensuring that the temperature deviation in the column box is minimal;
◆ High-precision dual-stable gas path, can simultaneously install four detectors.
◆ Temperature Control Indicators
Temperature control range: Room temperature 5℃~400℃ Increment 0.1℃
Temperature control accuracy: Better than ±0.01℃
Temperature programming: Inter-stage constant temperature time 0~999min Increment 0.1min Temperature increment 0.1℃
Heating rate: Maximum 40℃/min below 200℃ Maximum 20℃/min above 200℃
◆ Main Technical Indicators of Detectors
Hydrogen Flame Ionization Detector (FID)
1) Cylindrical collector electrode structure design, quartz nozzle, extremely high response
2) Detection limit: ≤8×10g/s (n-hexadecane/isooctane)
3) Baseline noise: ≤2×10A
◆ Thermal Conductivity Detector (TCD)
1) Using a semi-diffusion structure
2) The power supply adopts a constant current control method
3) Sensitivity: ≥8000mV•ml/mg (n-hexadecane/isooctane)
4) Baseline noise: ≤20μV