NR-BX/GX (Variable Frequency/Power Frequency) Series Resonance Test Equipment

Used for withstand voltage tests of capacitive test pieces with large capacity and high voltage, such as high-voltage cables, generators, large transformers, GIS, and CVT.


Messages

Product patent

Product description

Product Introduction

  Used for withstand voltage testing of capacitive test pieces with large capacity and high voltage, such as high-voltage cables, generators, large transformers, GIS, and CVT. When performing AC withstand voltage tests on large-capacity test pieces, the testing equipment often needs to have a large capacity as well, resulting in bulky equipment weighing tons, making transportation extremely inconvenient, especially unsuitable for on-site testing. To address this issue, our company has developed the NR-BX series variable frequency resonant testing equipment and NR-GX series power frequency resonant testing equipment. The variable frequency resonant testing equipment adjusts the power supply frequency, while the power frequency resonant testing equipment adjusts the reactor to achieve resonance between the reactor and the capacitive test piece, thereby obtaining high voltage and large current on the test piece. The variable frequency main unit uses a dedicated SPWM digital waveform generation chip, with small waveform distortion and stable frequency; it uses a quadrature asynchronous fixed-carrier modulation method to ensure good output waveform in the entire frequency range; the power part uses an advanced IPM module to ensure instrument stability and safety with minimum weight. The variable frequency resonant boosting device consists of a frequency-adjustable voltage regulator, an excitation transformer, a reactor, and a capacitive voltage divider. During the design process, the equipment requires that the weight of components that can be moved on-site by a single person does not exceed 30kg, and the weight of components that can be moved on-site by two people does not exceed 60kg, suitable for on-site transportation; the reactor part uses dry epoxy casting, which is beautiful and reliable, and meets the requirements of AC withstand voltage testing for various large-capacity test pieces.

Main Features

  ◆ Simple operation: Two modes, automatic testing (automatic resonance point search and automatic voltage increase) and manual testing (manual resonance point search and manual voltage increase), adapt to different testing requirements;

  ◆ Can set test voltage, frequency adjustment range, protection current, and pressurization time;

  ◆ Software fine-tuning of frequency and voltage;

  ◆ Has grounding and flashover protection functions;

  ◆ Can automatically track changes in grid voltage and adjust voltage in real time to maintain stable high voltage;

  ◆ Small size and light weight.

Technical Parameters

  ◆ Rated output voltage: 0~1000kV

  ◆ Output frequency: 30~300Hz

  ◆ Resonant voltage waveform: Pure sine wave, waveform distortion rate <1.0%

  ◆ Continuous operating time: 30min continuous operating time under full power output

  ◆ Quality factor: 30~90

  ◆ Frequency adjustment sensitivity: 0.1Hz, instability <0.5%

  ◆ Operating power supply: 220V/380V±15%,50Hz±5%

  Series product configuration and applicable range/cable

 

Product Model Name
Detailed Product Configuration
Variable Frequency Source
Reactor
Excitation Transformer
Applicable Range
NR-BX-44/22
2.5kW
1A/22kV two units
2.5kVA
10kV cable ≤1kM(300m㎡)
NR-BX-88/22
4kW
2A/22kV two units
4kVA
10kV cable ≤2kM(300m㎡)
NR-BX-132/22
6kW
2A/22kV three units
6kVA
10kV cable ≤3kM(300m㎡)
35kV cable ≤1kM(300m㎡)
NR-BX-176/22
7.5kW
2A/22kV four units
7.5kVA
10kV cable ≤4kM(300m㎡)
35kV cable ≤1kM(300m㎡)
NR-BX-264/22
10kW
2A/22kV six units
10kVA
10kV cable ≤6kM(300m㎡)
35kV cable ≤2kM(300m㎡)
NR-BX-330/22
15kW
2.5A/22kV six units
15kVA
10kV cable ≤8kM(300m㎡)
35kV cable ≤2kM(300m㎡)
Also applicable for 10-35kV switches and transformers
NR-BX-640/32
25kW
2.5A/32kV eight units
25kVA
10kV cable ≤10kM(300m㎡)
35kV cable ≤4kM (300m㎡)
110kV cable ≤1kM (400m㎡)
Compatible with 35-110kV GIS
NR-BX-1280/32
50kW
5A/32kV eight units
50kVA
10kV cable ≤20kM (300m㎡)
35kV cable ≤8kM (300m㎡)
110kV cable ≤2kM (400m㎡)
Compatible with 35kV-110kV GIS
NR-BX-1950/130
100kW
3.75A/130kV four units
100kVA
110kV main transformer, switchgear, cable ≤2.5kM; 220kV GIS
NR-BX-3250/130
150kW
6.25A/130kV four units
150kVA
110kV cable ≤5kM; 110kV-220kV main transformer, switchgear, GIS

 

  ◆ Scope of application: Without special instructions, the cable length of 10kV given in the table above is 2.0 times the withstand voltage under the condition of 30~300Hz. If it is 2.5 times the withstand voltage, the cable length should be reduced by 33% accordingly. Users can optionally configure compensating capacitors and protective spark gaps.

  Substation equipment

 

Product Model Name
Detailed Product Configuration
Variable Frequency Source
Reactor
Excitation Transformer
Test object and scope of application
NR-BX-108/108
5kW
27kV/1A four units
5kVA
Power transformers, circuit breakers, busbars, and insulators at 35kV and below voltage levels; 10kV (300 m㎡) cable 2kM; 35kV (300 m㎡) cable 0.3kM
NR-BX-135/108
7.5kW
27kV/1.25A four units
7.5kVA
10kV (300 m㎡) cable 3kM; 35kV (300 m㎡) cable 0.5kM; 35kV switchgear, insulators, etc.
NR-BX-216/216
10kW
54kV/1A four units
10kVA
110kV fully insulated main transformer, circuit breaker, busbar, GIS ≤10 sections; 35kV (300 m㎡) cable 1kM; 10kV (300 m㎡) cable 3kM
NR-BX-270/270
15kW
54kV/1A five units
15kVA
110kV main transformer, switchgear, GIS; 35kV cable ≤1.5kM; 10kV cable ≤5kM
NR-BX-200/400
10kW
100kV/0.5 four units
10kVA
220kV switchgear, GIS; 110kV main transformer, switchgear, GIS
NR-BX-400/400
20kW
100kV/1A four units
20kVA
35-220kV main transformer, switchgear, GIS; 35kV cable ≤1kM; 10kV cable ≤4kM
NR-BX-520/260
25kW
65kV/2A four units
25kVA
110kV fully insulated main transformer, circuit breaker, busbar, GIS ≤10 sections, (300 m㎡) cable 0.8 kM; 35kV (300 m㎡) cable 3kM; 10kV (300 m㎡) cable 6kM
NR-BX-500/500
 

20kW
125kV/1A four units
20kVA
220kV and below voltage transformers, current transformers, bushing, post insulators, isolating switches, circuit breakers, insulating tools
NR-BX-600/600
30kW
120kV/1A five units
30kVA
35-220kV main transformer, switchgear, GIS, insulators; 110kV cable ≤0.8kM; 35kV cable ≤1.1kM
NR-BX-1600/800
60kW
200kV/2A four units
60kVA
35-500kV main transformer, switchgear, GIS, insulators; 220kV cable ≤0.5kM; 110kV cable ≤0.8kM

  Generator

Product Model Name
Applicable generator capacity
Number of reactor units
NR-GX-200/25
Generator 0.4~1.0uF (10kV/40MW)
200kVA/25kV adjustable reactor one unit
NR-GX-300/50
Generator 0.27~0.33Uf (20kV/300MW)
300kVA/50kV adjustable reactor One unit
NR-GX-600/50
Generator 0.113~0.45uF (20kV/600MW)
200kVA/50kV fixed reactor one unit: 400kVA/50kV adjustable reactor one unit
NR-GX-1200/50
Generator 0.6~1.8uF (20kV/250MW)
200kVA/50kV fixed reactor two units: 800kVA/50kV adjustable reactor one unit

 

  ◆ Due to the relatively small adjustment range of power frequency resonance, there are certain gaps in the table above, which can be adjusted according to the actual generator capacity and test voltage level.

  ◆ The above listed models are some of the company's conventional products. If different configurations are required, different configurations can be customized according to the parameters of the test sample.