  • 385e80f7887fe1838bcd738b261a2a5.jpg

NR5600系列全自动电容电感测试仪

Power systems usually use parallel capacitor banks to improve the power factor in order to reduce reactive power losses. In practical applications, the failure rate of capacitor compensation devices is relatively high, which is determined by the characteristics of the working state of the capacitor device. Therefore, it is very important to regularly inspect capacitor devices, detect capacitor defects early, and prevent the expansion of faults. The fully automatic capacitance and inductance tester can measure individual capacitors connected in parallel groups without disconnecting the wires, and it can also measure inductance. It is convenient to connect and easy to operate, greatly improving the efficiency of on-site testing. It can also avoid the possibility of errors caused by the disassembly and installation of leads.


Messages

Product patent

Product description

Product Introduction
  Power systems usually use parallel capacitor banks to improve the power factor in order to reduce reactive power losses. In practical applications, the failure rate of capacitor compensation devices is relatively high, which is determined by the characteristics of the working state of the capacitor device. Therefore, it is very important to regularly inspect capacitor devices, detect capacitor defects early, and prevent the expansion of faults. The fully automatic capacitance and inductance tester can measure individual capacitors connected in parallel groups without disconnecting the wires, and it can also measure inductance. It is convenient to connect and easy to operate, greatly improving the efficiency of on-site testing. It can also avoid the possibility of errors caused by removing and installing leads.
 
Main Features
  ◆ Measuring capacitors on-site requires removing connecting wires, which is not only labor-intensive but also easily damages capacitors;
  ◆ The low output voltage of the capacitance meter leads to a low fault detection rate;
  ◆ This instrument has the characteristics of small measurement workload, quick and convenient operation, stable performance, accurate measurement, and high fault detection rate.
 
Technical Parameters
  a. Capacitance Measurement (1) Measurable capacitance range: 0.1μF~3300μF;
  (2) Measurable capacity range: 5~20,000kvar;
  (3) Measurement Accuracy: ±(1.5% reading ±0.1μF);
  (4) Resolution: ±1.0%rdg;
  b. Current Measurement (1) Current measurement range: 0~1000A;
  (2) Measurement accuracy: ±1.5%;
  c. Inductance Measurement (1) Inductance measurement range: 0.1mH~50H
  (2) Measurement accuracy: ±(3.0% reading + 0.1 mH)
  (3) Resolution: 0.01mH
  Working Power Supply: Rated voltage: 50Hz 220V±10%;
  ◆ Display and printing method: LCD screen with full Chinese characters display, panel-type high-speed printer
  ◆ Display and printing method: LCD screen with full Chinese characters display, panel-type high-speed printer
  ◆ Dimensions/Weight: 370mm*260mm*220mm / 8 kg
 
 

SAUNDERS

If you have any suggestions or feedback on our company, please fill in the relevant information on this page and submit it. A staff member will contact you in time, or please call us directly.


Submit