Product
NR8500 Series Transformer Oil Chromatography Online Monitoring System
The NR8500 series transformer oil chromatography online monitoring system (multi-component) is used to measure and analyze trace characteristic gases contained in the insulating oil of oil-immersed electrical equipment. By analyzing the gas content, it can capture potential latent fault information in the equipment in real time and ensure reliable operation of the equipment.
Category:
Email:
Messages
Product description
|
Category |
Parameter |
Device |
|
Power Characteristics |
AC: V |
220
|
|
Frequency: Hz |
50±1 |
|
|
Environmental Parameters |
Device |
|
|
Operating Temperature |
-45~70oC |
|
|
Operating Environment Humidity |
5-95% No Condensation |
|
|
Seismic Resistance |
Grade 8 |
|
|
Analysis Cycle |
50 minutes to complete one monitoring process, continuous monitoring is possible |
|
|
Carrier Gas |
High-purity air |
|
|
Electrical Safety |
Dielectric Strength: V |
100, 500, 1000, 1500 (1min) |
|
Insulation Resistance: MΩ |
AC circuit external terminal to ground ≥10; ungrounded DC circuit (excluding sensor) to ground ≥1 |
|
◆ System Monitoring Parameters
| Serial Number |
Gas |
Minimum detectable gas concentration |
Monitoring Range |
Monitoring Accuracy |
Repeatability of the same oil sample |
| 1 |
H2 |
1uL/L |
1-5000uL/L |
±10% 2uL/L, whichever is larger |
Less than ±5% |
| 2 |
CO |
1uL/L |
1-5000uL/L |
±10% |
Less than ±5% |
| 3 |
CH4 |
0.5uL/L |
0.5-4000uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 4 |
C2H6 |
0.5uL/L |
0.5-3000uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 5 |
C2H4 |
0.5uL/L |
0.5-4000uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 6 |
C2H2 |
0.1uL/L |
0.1-2000uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 7 |
CO2 |
10uL/L |
10-5000uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 8 |
Trace Water (Optional) |
1uL/L |
1-100uL/L |
±10% or 2uL/L, whichever is larger |
Less than ±5% |
| 9 |
Water Activity (Optional) |
0.01 |
0-1aw |
±0.02 |
Less than ±5% |
| 10 |
Oil Temperature (Optional) |
|
-40~180℃ |
±0.01℃ |
Less than ±5% |
| 11 |
Total Hydrocarbons (Optional) |
0.1uL/L |
0.1-8000uL/L |
The greater of ±5% or 2uL/L |
Less than ±5% |
Previous page
Recommended products
SAUNDERS